Product Overview
| Suitable Applications | Premise Horizontal Cable, Ethernet 1000BASE-T, Ethernet 100BASE-TX, Ethernet 10BASE-T, PoE++, PoE+, PoE , Noisy Environments |
|---|
Construction Details
CONDUCTOR
| Size | Stranding | Material | No. of Pairs |
|---|---|---|---|
| 24 AWG | Solid | BC – Bare Copper | 4 |
INSULATION
| Material | Color Code |
|---|---|
| FEP – Fluorinated Ethylene Propylene | White/Blue Stripe & Blue, White/Orange Stripe & Orange, White/Green Stripe & Green, White/Brown Stripe & Brown |
OUTER SHIELD
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Polyester + Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
OUTER JACKET
| Material | Material Trade Name | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | FlamarrestĀ® | 0.235 in (5.97 mm) | No |
| Overall Cable Diameter (Nominal) | 0.235 in (5.97 mm) |
|---|
Electrical Characteristics
ELECTRICALS
| Max. Conductor DCR | Max. Capacitance Unbalance |
|---|---|
| 93.8 Ohm/km (28.6 Ohm/1000ft) | 330 pF/100m |
DELAY
| Frequency | Max. Delay | Max. Delay Skew | Nom. Velocity of Prop. |
|---|---|---|---|
| 100 MHz | 537.6 ns/100m | 45 ns/100m | 70% |
HIGH FREQUENCY
| Frequency [MHz] | Max. Insertion Loss (Attenuation) | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Max./Min. Input Impedance (unFitted) [Ohm] | Max./Min. Fitted Impedance [Ohm] |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 2.0 dB/100m | 65.3 | 62.3 | 63.3 | 60.3 | 63.8 | 60.8 | 20.0 | 100 ± 15 | 100 ± 15 |
| 4 | 4.1 dB/100m | 56.3 | 53.3 | 52.2 | 49.2 | 51.8 | 48.8 | 23.0 | 100 ± 15 | 100 ± 15 |
| 8 | 5.8 dB/100m | 51.8 | 48.8 | 46.0 | 43.0 | 45.7 | 42.7 | 24.5 | 100 ± 15 | 100 ± 15 |
| 10 | 6.5 dB/100m | 50.3 | 47.3 | 43.8 | 40.8 | 43.8 | 40.8 | 25.0 | 100 ± 15 | 100 ± 15 |
| 16 | 8.2 dB/100m | 47.2 | 44.2 | 39.0 | 36.0 | 39.7 | 36.7 | 25.0 | 100 ± 15 | 100 ± 15 |
| 20 | 9.3 dB/100m | 45.8 | 42.8 | 36.5 | 33.5 | 37.8 | 34.8 | 25.0 | 100 ± 15 | 100 ± 15 |
| 25 | 10.4 dB/100m | 44.3 | 41.3 | 33.9 | 30.9 | 35.8 | 32.8 | 24.3 | 100 ± 15 | 100 ± 15 |
| 31.25 | 11.7 dB/100m | 42.9 | 39.9 | 31.2 | 28.2 | 33.9 | 30.9 | 23.6 | 100 ± 15 | 100 ± 15 |
| 62.5 | 17.0 dB/100m | 38.4 | 35.4 | 21.4 | 18.4 | 27.9 | 24.9 | 21.5 | 100 ± 15 | 100 ± 15 |
| 100 | 22.0 dB/100m | 35.3 | 32.3 | 13.3 | 10.3 | 23.8 | 20.8 | 20.1 | 100 ± 15 | 100 ± 15 |
| 155 | 28.1 dB/100m | 32.4 | 29.4 | 4.4 | 1.4 | 20.0 | 17.0 | 18.8 | ||
| 200 | 32.4 dB/100m | 30.8 | 27.8 | 17.8 | 14.8 | 18.0 |
VOLTAGE
| UL Voltage Rating |
|---|
| 300 V (CMP) |
Mechanical Characteristics
TEMPERATURE
| UL Temperature | Operating | Installation | Storage |
|---|---|---|---|
| 75°C | -20°C To +75°C | 0°C To +50°C | -20°C To +75°C |
BEND RADIUS
| Stationary Min. | Installation Min. |
|---|---|
| 2.0 in (51 mm) | 2.5 in (64 mm) |
| Max. Pull Tension | 25 lbs (11 kg) |
|---|---|
| Bulk Cable Weight | 32 lbs/1000ft |
Standards and Compliance
| Environmental Suitability | Plenum, Indoor |
|---|---|
| Sustainability | Product Lensā¢, Environmental Product Declaration (EPD) Available |
| Flammability / Reaction to Fire | NFPA 262, UL 910 (Plenum), FT6, IEC 60332-1-2 |
| CPR Compliance | CPR Euroclass: Eca; CPR UKCA Class: Eca |
| NEC / UL Compliance | Article 800, CMP |
| CEC / C(UL) Compliance | CMP |
| ICEA Compliance | S-90-661 |
| IEEE Compliance | IEEE 802.3bt Type 1, Type 2, Type 3 |
| NEMA Compliance | NEMA WC-63.1 |
| Data Category | Category 5e |
| TIA/EIA Compliance | ANSI/TIA-568.2-D Category 5e |
| Third Party Performance Verification | Category 5e |
| ISO/IEC Compliance | ISO/IEC 11801-1, IEC 61156-5 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE), REACH: 2020-01-16 |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number | 1533R |
Product Notes
| Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. Values above 100 MHz are for Engineering Information Only. The shield is Bonded to Jacket’s Inner Wall for Electrical Stability. Print Includes Descending Footage Markings from Max. Put-Up Length to 0. |
|---|