Product Overview
| Suitable Applications | Premise Horizontal Cable, Ethernet 1000BASE-T, Ethernet 100BASE-TX, Ethernet 10BASE-T, PoE++, PoE+, PoE, Environments Requiring Limited Combustible Cable |
|---|---|
| Patent | This product has one or more applicable patents. |
Construction Details
CONDUCTOR
| Size | Stranding | Material | No. of Pairs |
|---|---|---|---|
| 23 AWG | Solid | BC – Bare Copper | 4 |
INSULATION
| Material | Color Code |
|---|---|
| FEP – Fluorinated Ethylene Propylene | White/Blue Stripe & Blue, White/Orange Stripe & Orange, White/Green Stripe & Green, White/Brown Stripe & Brown |
| Bonded-Pair | Yes |
|---|
OUTER JACKET
| Separator | Material | Nom. Diameter | Ripcord |
|---|---|---|---|
| Central Filler | FEP – Fluorinated Ethylene Propylene | 0.210 in (5.33 mm) | No |
| Overall Cable Diameter (Nominal) | 0.210 in (5.33 mm) |
|---|
Electrical Characteristics
ELECTRICALS
| Max. Conductor DCR | Max. Capacitance Unbalance |
|---|---|
| 82 Ohm/km (25 Ohm/1000ft) | 90 pF/100m |
DELAY
| Max. Delay | Max. Delay Skew | Nom. The velocity of Prop. |
|---|---|---|
| 537 ns/100m | 45 ns/100m | 72% |
HIGH FREQUENCY
| Frequency [MHz] | Max. Insertion Loss (Attenuation) | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Max./Min. Input Impedance (unFitted) [Ohm] | Max./Min. Fitted Impedance [Ohm] |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 2.0 dB/100m | 74.3 | 72.3 | 72.3 | 70.3 | 67.8 | 64.8 | 20 | 100 ± 15 | 100 ± 15 |
| 4 | 3.8 dB/100m | 65.3 | 63.3 | 61.5 | 59.5 | 55.8 | 52.8 | 23 | 100 ± 15 | 100 ± 15 |
| 8 | 5.3 dB/100m | 60.8 | 58.8 | 55.4 | 53.4 | 49.7 | 46.7 | 24.5 | 100 ± 15 | 100 ± 15 |
| 10 | 6 dB/100m | 59.3 | 57.3 | 53.3 | 51.3 | 47.8 | 44.8 | 25 | 100 ± 15 | 100 ± 15 |
| 16 | 7.6 dB/100m | 56.2 | 54.3 | 48.7 | 46.7 | 43.7 | 40.7 | 25 | 100 ± 15 | 100 ± 15 |
| 20 | 8.5 dB/100m | 54.8 | 52.8 | 46.3 | 44.3 | 41.8 | 38.8 | 25 | 100 ± 15 | 100 ± 15 |
| 25 | 9.5 dB/100m | 53.3 | 51.3 | 43.8 | 41.8 | 39.8 | 36.8 | 24.3 | 100 ± 15 | 100 ± 15 |
| 31.25 | 10.7 dB/100m | 51.9 | 49.9 | 41.2 | 39.2 | 37.9 | 34.9 | 23.6 | 100 ± 15 | 100 ± 15 |
| 62.5 | 15.4 dB/100m | 47.4 | 45.4 | 32 | 30 | 31.9 | 28.9 | 21.5 | 100 ± 15 | 100 ± 15 |
| 100 | 19.8 dB/100m | 44.3 | 42.3 | 24.5 | 22.5 | 27.8 | 24.8 | 20.1 | 100 ± 15 | 100 ± 15 |
| 155 | 25.2 dB/100m | 41.5 | 39.5 | 16.3 | 14.3 | 23.9 | 20.9 | 18.8 | 100 ± 22 | 100 ± 15 |
| 200 | 29.0 dB/100m | 39.8 | 37.8 | 10.8 | 8.8 | 21.8 | 18.8 | 18 | 100 ± 22 | 100 ± 15 |
| 250 | 32.8 dB/100m | 38.3 | 36.3 | 5.5 | 3.5 | 19.8 | 16.8 | 17.3 | 100 ± 32 | 100 ± 15 |
VOLTAGE
| UL Voltage Rating |
|---|
| 300 V (CMP) |
Mechanical Characteristics
TEMPERATURE
| Operating | Installation | Storage |
|---|---|---|
| -40°C To +150°C | 0°C To +50°C | -20°C To +75°C |
BEND RADIUS
| Stationary Min. | Installation Min. |
|---|---|
| 0.5 in (13 mm) | 2.1 in (53 mm) |
| Max. Pull Tension | 40 lbs (18 kg) |
|---|---|
| Bulk Cable Weight | 33 lbs/1000ft |
Standards and Compliance
| Environmental Suitability | Plenum, Indoor |
|---|---|
| Flammability / Reaction to Fire | NFPA 262 Plenum Flame Test (UL910),UL723 (NFPA 255), FT6, IEC 60332-1-2 |
| CPR Compliance | CPR Euroclass: Eca |
| NEC / UL Compliance | Article 800, CMP |
| CEC / C(UL) Compliance | CMP |
| ICEA Compliance | S-116-732 |
| IEEE Compliance | IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 |
| Data Category | Category 6 |
| TIA/EIA Compliance | ANSI/TIA-568.2-D Category 6 |
| Third Party Performance Verification | Category 6 |
| ISO/IEC Compliance | ISO/IEC 11801-1, IEC 61156-5 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE), REACH: 2020-01-16 |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number | 2412 |
Product Notes
| Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. Jacket sequentially marked at 2 ft. intervals. |
|---|