Product Overview
Environmental Space | Indoor/Outdoor – Euroclass Dca |
---|---|
Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser), and horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV, and broadcast. Easy to install in ducts, tunnels, and trenches, and/or tubes. Suitable for Direct Burial. |
Construction
FIBER CABLE CONSTRUCTION
Fiber Type | Fiber Count | Subunit Color |
---|---|---|
OM3 | 6 | TIA coding (Gxxxxxx.T): Natural |
Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White |
---|
Cable Core Water Tight | Yes |
---|---|
Cable Core Waterblocking | Water blocking Glass Yarns + Tape |
Bulk Cable Weight | 148 kg/km |
SubUnit Specifications
Number of Active Subunits | 1 |
---|---|
Number of Subunit Positions | 1 |
Fibers Per Subunit | 6 |
Jacket Specifications
Number of Jackets | Single Jacket |
---|---|
Type of Armor | Corrugated Steel Tape |
Outer Jacket Specifications
OUTER JACKET
Material | Nominal Diameter | Ripcord |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 10.6 mm | Yes |
Table Notes | Standard color: Black. Available colors: Black, Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Lime Green |
---|
Optical Characteristics
Max. Attenuation at 1300 nm | 0.9 dB/km |
---|---|
Max. Attenuation at 850 nm | 2.9 dB/km |
Mechanical Characteristics
MECHANICAL TESTS
Description | Tested Standard | Requirement/Value | According to Family Specification |
---|---|---|---|
Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 212 mm | IEC 60794-3-10 |
Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 212 mm | IEC 60794-3-10 |
Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 4350 N (978 lbf) | IEC 60794-3-10 |
Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 1450 N (326 lbf) | IEC 60794-3-10 |
Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 22 kN/m | IEC 60794-3-10 |
Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 11 kN/m | IEC 60794-3-10 |
Temperature Range
Operating Temperature Range | -30 °C to +70 °C |
---|---|
Installation Temperature Range | -5 °C to +50 °C |
Storage Temperature Range | -30 °C to +70 °C |
Standards
UL Rating/Flame Test | Non-UL Rated |
---|---|
IEC Flammability | IEC 60332-1-2 |
Reaction to Fire – Bundle Flame Test | IEC 60332-3-22 |
Resistance to Fire-Circuit Integrity | IEC 60331-25-E120 / EN 50200-PH120 |
IEC 60754-1 – Halogen Amount | Zero |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity | 10 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH | 4.3 |
IEC 61034-2 – Smoke Density Min. Transmittance | 60% |
CPR Euroclass | Dca-s2,d1,a1 |
REACH | Compliant |
ISO/IEC Compliance | IEC 60794 |
Safety Listing | LUL 1-085 |
UV/ Sunlight Protection | Yes |